Structure

Dome nut

Polyamide PA6 V-0

Sealing ring

Polychloroprene-Nitrile rubber CR/NBR

Gland body

Polyamide PA6 V-0

Connecting thread

metric, as per EN 60423

Properties

  • for superior claims on firing protection
  • Polyamide material fulfills UL 94 V-0 and EN 45545-2, R22:HL3 / R23: HL3
  • integrated anchorage
  • wide sealing and clamping range
  • easy-to-install
  • UV- and weather resistance according UL 514B
Temperature range
  • -20 °C / +100 °C (dynamic)
  • -40 °C (static, short term)
Protection grade

IP68

Test standard

UL 514B

Comment
  • details about tests results - see annex,
  • hexagonal locknuts of polyamide PA6 V-0 see 50.2xx PA/FLzzzz,
  • Catalog Page 57
UL / CSA-File

E140310

DNV Certificate

TAE000037X

Connecting thread standard length

RAL 7035 / lichtgrau RAL 7035 / lichtgrau

Part numberAØCLSW1SW2HPacking unit VPE
50.612 PA/FL7035M12x1,53 - 6,58151531100 Stück
50.616 PA/FL7035M16x1,55 - 108202035,5100 Stück
50.620 PA/FL7035M20x1,58 - 138242436100 Stück
50.625 PA/FL7035M25x1,511 - 17829294350 Stück
50.632 PA/FL7035M32x1,515 - 211036365025 Stück
50.640 PA/FL7035M40x1,519 - 281046465110 Stück
50.650 PA/FL7035M50x1,527 - 3512555561,55 Stück
50.663 PA/FL7035M63x1,532 - 4212686865,55 Stück

RAL 9005 / tiefschwarz RAL 9005 / tiefschwarz

Part numberAØCLSW1SW2HPacking unit VPE
50.612 PA/FLSWM12x1,53 - 6,58151531100 Stück
50.616 PA/FLSWM16x1,55 - 108202035,5100 Stück
50.620 PA/FLSWM20x1,58 - 138242436100 Stück
50.625 PA/FLSWM25x1,511 - 17829294350 Stück
50.632 PA/FLSWM32x1,515 - 211036365025 Stück
50.640 PA/FLSWM40x1,519 - 281046465110 Stück
50.650 PA/FLSWM50x1,527 - 3512555561,55 Stück
50.663 PA/FLSWM63x1,532 - 4212686865,55 Stück

Comment: All listed parts- are in accordance with EN 45545-2, clause 4.5 "Non-listed products" with - exposed areas ≤ 0.20 m2, location interior, R22- exposed areas ≤ 0.20 m2, location exterior, R23- have according to EN 45545-2, clause 4.3.2, Rule 1 total, combustible / flammable mass of the products< 100 g for grouped products, location interior < 400 g für grouped products, location exterior.