Manufacturer information

For more information about this product, please visit the following link.

Product information as PDF

Here you can download the product data sheet as a PDF.

Description

Specially designed for the extremely demanding requirements of higher power applications. The inserts are available with 1 to 4 contacts with a conductor acceptance range of between 50,0 mm² and 630,0 mm² operating up to 780 A and 750 V. Other voltages available on request.

Available materials
  • Brass
  • Brass, nickel-plated
  • Edelstahl 1.4404 / 316L
Approvals
  • ATEX/ IECEx
  • NEC/ CEC / CSA / UL
  • CCC
  • EAC
  • EQM
  • Inmetro
  • PESO
  • SONCAP
Marine Approvals
  • DNV
  • Bureau Veritas
  • ABS
Zones & Gas Groups
  • Zone 1
  • Zone 2
  • Zone 21
  • Zone 22
  • Gasgruppen IIA, IIB und IIC
Pins

von 1 bis 4

Cross section

von 50 mm² bis 630 mm²

Maximum voltage

750 V

Protection grade
  • IP66
  • IP67
  • Deluge Protected DTS01
Test standard
  • EN IEC 60079-0
  • EN IEC 60079-1
  • EN IEC 60079-31
Remark

Product design and specifications are subject to change without notice. Please check with Jacob GmbH or the manufacturers website for latest specification.

Maximum power

780 A

Marking
  • Ex db IIC Gb T5/T6
  • Ex tb IIC Db T95/T80
Temperature range

-40 °C / +60 °C